3 Phase Generator Size Calculator

Calculate the appropriate size three-phase generator needed for commercial, industrial, or large residential applications by entering your electrical loads below.

System Information

Motor Loads

Added Motors

Lighting and Receptacle Loads

HVAC Loads

Special Loads

Add Custom 3-Phase Loads

Added Custom Loads

About 3 Phase Generator Sizing

Selecting the right size three-phase generator for commercial or industrial applications requires careful calculation of all connected loads, with special consideration for motor starting requirements and power factor. Our calculator helps you determine the appropriate generator capacity based on your specific electrical system requirements.

3 Phase Generator Size Guide

Generator Size Application Typical Coverage
30-50 kW Small Commercial Retail stores, small offices
60-100 kW Medium Commercial Restaurants, medical offices, schools
125-250 kW Large Commercial Hotels, supermarkets, data centers
300-500 kW Industrial Manufacturing, warehouses
600-2000 kW Large Industrial Hospitals, factories, high-rises

Common 3-Phase Power Requirements

Equipment Running kW Starting kVA Power Factor
20 HP Motor (Direct Start) 15 kW 90 kVA 0.85
50 HP Motor (Soft Start) 37 kW 75 kVA 0.87
100 Ton Chiller 90 kW 300 kVA 0.82
Elevator (10 HP) 7.5 kW 45 kVA 0.75
Welding Machine 25 kW 30 kVA 0.65
LED Lighting (1000 fixtures) 15 kW 15 kVA 0.95

Essential Considerations for 3-Phase Generators

1. Motor Starting Methods

Different motor starting methods significantly impact generator sizing:

Starting Method Starting Current Impact on Generator Typical Applications
Direct Online (DOL) 600-800% FLA High surge requirement Small motors, pumps
Star-Delta 200-300% FLA Reduced surge Medium motors, fans
Soft Starter 150-300% FLA Gentle ramp-up Conveyors, compressors
Variable Frequency Drive 100-150% FLA Minimal surge Precision control systems

2. Power Factor Considerations

Understanding power factor is crucial for proper generator sizing:

  • Definition: Ratio of real power (kW) to apparent power (kVA)
  • Typical Values:
    • Motors: 0.8-0.9
    • Lighting: 0.95-1.0
    • Welding: 0.5-0.7
    • Computers: 0.6-0.7
  • Generator Impact: Low power factor loads require larger generators
  • Correction: Capacitor banks can improve power factor

3. Voltage Dip Requirements

Critical systems have strict voltage dip limitations:

Application Max Voltage Dip Recovery Time Generator Considerations
Data Centers 10% <100ms UPS required
Medical Facilities 15% <500ms High inertia generator
Manufacturing 20% <1s Soft starters recommended
Commercial Buildings 25% <2s Standard generator acceptable

Frequently Asked Questions

How does three-phase generator sizing differ from single-phase?

Three-phase generator sizing has unique considerations:

  • Power calculations use √3 (1.732) factor for line voltage
  • Motor starting currents are more critical
  • Load balancing across phases is important
  • Power factor has greater impact on sizing
  • Harmonic distortion may need consideration

What's the difference between standby and prime power ratings?

Generator ratings vary by application:

  • Standby: For emergency use, limited run time
  • Prime: Continuous operation, unlimited hours
  • Continuous: Same as prime but with 10% overload
  • Standby ratings are typically 10-15% higher than prime

How do I account for harmonic loads in generator sizing?

For non-linear loads with harmonics:

  • Add 20-30% capacity for moderate harmonic distortion
  • Consider derating generator by 15-20% for high THD
  • Specify generator with low subtransient reactance
  • Install harmonic filters if THD > 10%

What size generator do I need for multiple motors?

For multiple motor applications:

  • Sum all running kW requirements
  • Add largest starting kVA to running kVA of others
  • Consider staggered starting sequence
  • Add 25% margin for future expansion

How does ambient temperature affect generator sizing?

Temperature impacts generator performance:

  • Above 40°C (104°F): Derate 1% per 1°C over 40°C
  • High altitude: Additional derating required
  • Humidity: Affects cooling efficiency
  • Enclosure type: Impacts cooling capability

Should I size for peak or average demand?

Generator sizing should consider:

  • Peak demand for worst-case scenario
  • Diversity factor for non-coincident loads
  • Load sequencing possibilities
  • Future expansion requirements

How do I calculate generator size for data centers?

Data center generator considerations:

  • N+1 redundancy for critical loads
  • 2N configuration for high availability
  • Include UPS recharge current
  • Account for cooling system loads

What's the impact of voltage regulation on generator sizing?

Voltage regulation affects:

  • Motor starting capability
  • Sensitive equipment performance
  • Generator transient response
  • Need for voltage regulators

How do I size a generator for a chiller plant?

Chiller plant considerations:

  • Include all chiller components (compressors, pumps)
  • Account for across-the-line or soft starter
  • Consider lead/lag sequencing
  • Add cooling tower fan loads

What's the difference between kVA and kW in generator sizing?

Understanding power measurements:

  • kW (kilowatts): Real power doing work
  • kVA (kilovolt-amperes): Apparent power
  • Relationship: kW = kVA × power factor
  • Generators are typically rated in kVA

How do I account for future expansion in generator sizing?

Planning for growth:

  • Add 20-25% capacity margin
  • Consider modular generator systems
  • Plan for paralleling capability
  • Ensure physical space for expansion

What's the impact of load sequencing on generator size?

Load sequencing benefits:

  • Reduces required generator size
  • Manages inrush currents
  • Prioritizes critical loads
  • Can be automated with PLC controls

How do I size a generator for a healthcare facility?

Healthcare specific requirements:

  • Life safety and critical branches
  • Equipment branches per NEC 517
  • Strict voltage regulation needs
  • Redundancy requirements

What's the impact of generator transient response on sizing?

Transient response considerations:

  • Affects voltage dip during motor starts
  • Subtransient reactance (X"d) important
  • Higher inertia rotors better for motor loads
  • May require oversizing for sensitive loads

How do I calculate generator size for a manufacturing plant?

Manufacturing plant specifics:

  • Inventory all motor loads
  • Consider production line sequencing
  • Account for welding loads separately
  • Include compressed air systems